| Option 1 |
HOA Selector keypad
|
|---|
| Width |
260 mm
|
|---|---|
| Height |
217.83 mm
|
| Depth |
166.5 mm
|
| Number of poles |
Power circuit: 3
|
| Wire size |
Power terminal: (2) #18... AWG (0.8...5.2 mm²) per terminal
|
| Degree of protection (IP) |
IP66
|
|---|---|
| Shipping weight, approx |
4.6 kg
|
| Power rating |
Power terminal: 25A @ 600V AC
|
| Shock |
Opsal: 30 G, exceeds IEC 60947-1
|
| Gland plate options |
ArmorConnect power media connection (no cable)
|
| Wire strip length |
0.35 ±0.01 in (9 ±2 mm)
|
| Vibration |
Opsal: 2.5 G @ tested to MIL-STD-810G, exceeds IEC 60947-1
|
| Tightening torque |
Power terminal: 10.6 ±2 in-lb (1.2 ±0.2 Nm)
|
| Mechanical life operations |
Disconnect: 200000
|
| Disconnect lock out |
Maximum of 3/8 in (9.5 mm) diam lock shackle or hasp
|
| Contactor opening delay |
8 ms
|
| Contactor closing delay |
18 ms
|
| Wire type |
Multi-strand copper wire
|
| Disconnect LOTO locks |
Up to 2 locks or hasps are supported
|
| Contactor utilization category |
AC-1, AC-3, AC-4 per IEC (refer to life load curves)
|
| Baud rates |
500 kbps
|
|---|---|
| Communication |
DeviceNet
|
| Web server |
HTTP 1.1
|
| Input ON-state current (pin 4) |
2.6mA @ 24V DC
|
| DeviceNet input current surge |
500 mA @ peak inrush
|
| Operating dielectric withstand |
2000V AC per IEC
|
| DeviceNet input current |
50mA @ 24V DC
|
| Overvoltage category |
Power circuit: III
|
| Product type |
Full voltage starter
|
| Fuse rating |
CC, J, or T fuse (40 A, maximum)
|
| DeviceNet supply voltage rating |
Range 11...25V DC @ 24V DC nominal
|
| Insulation voltage (Ui) |
Output ratings: rated 2000V AC per IEC
|
| Rated operating current, max |
Power circuit: 0.24...3.5A @ 2Hp (1.5 kW)
|
| Rated input operation voltage |
24V DC
|
| Input OFF-state current |
<1.5 mA
|
| Input OFF-state voltage |
5V DC
|
| Distance, max |
500 m (1630 ft) @ 125 Kbps
|
| Operating frequency |
Power circuit: 50/60 Hz (±10%)
|
| User options 1 |
HAND-OFF-AUTO selector keypad
|
| Trip rating |
Power circuit: 120% of full load current (FLC) setting
|
| Application in industrial area permitted (SCPD list) |
Size per NFPA 70 (NEC) or NFPA 79 for group motor applications
|
| Short circuit coordination |
Type 1
|
| Overload type |
Power circuit: solid-state I²t
|
| Insulation voltage |
Rated 250V AC
|
| Dielectric withstand |
Power circuit: 2500V AC per IEC
|
| Concurrent TCP connections |
Network connections: maximum of 15 encapsulated messages over both TCP and UDP
|
| RMS symmetrical amperes |
10 kA @ 480Y/277 (short circuit current rating)
|
| Power |
Control circuit (external source): 6.6 W @ switched and unswitched power supply requirements
|
| Current, nom |
Control circuit (external source): 275 mA @ switched and unswitched power supply requirements
|
| Peak inrush |
Control circuit (external source): <5 A for 35 ms @ unswitched power supply requirements
|
| Voltage |
Control circuit (external source): 19.2...26.4V DC @ unswitched power supply requirements
|
| Trip class |
Power circuit: Class 10 (default), 15, 20 with thermal memory retention (see motor overload trip curves)
|
| Current, max |
Control circuit (external source): 450 mA @ unswitched power supply requirements
|
| Power, max |
Control circuit (external source): 6.6 W + (24V DC x user defined) @ switched and unswitched power supply requirements
|
| Supporting protocol for DeviceNet |
Yes
|
| Application in industrial area permitted |
Yes
|
| Mains frequency |
50/60 Hz
|
| Number of input devices, max |
6
|
| Output OFF-state leakage current, max |
1 µa
|
| Number of outputs, max |
6
|
| Number of configurable digital I/O |
6
|
| Input filtering |
100 µs
|
| OFF time, min |
200 ms
|
| Auto-baud rate identification |
Yes
|
| Group 2 - slave only device type |
Yes
|
| Polled I/O messaging |
Yes
|
| Change of state messaging |
Yes
|
| Cyclic messaging |
Yes
|
| Explicit messaging |
Yes
|
| Full parameter object support |
Yes
|
| Group 4 - off-line node recovery messaging |
Yes
|
| Configuring consistency value |
Yes
|
| Unconnected messaging manager (UCMN) |
Yes
|
| Output supply voltage (switched power) |
A1/A2
|
| Input per connection |
1/each
|
| Output per connection |
1/each
|
| Output blocking voltage, max |
35V DC
|
| Sensor input leakage current, max |
<2.5 mA
|
| Type of outputs |
DC sourcing
|
| Sensor input operating voltage |
19.2...26V DC
|
| Concurrent sessions |
Web server: 20
|
| Rated output operating voltage (Ue) |
19.2...26.4V DC
|
| Disconnect |
Motor disconnect
|
| Output operating current (Ie), nom |
500 mA per point
|
| Output thermal current (Ithe), max |
500 mA per point
|
| Connection type |
Quick disconnects
|
| Output state |
Normally open (NO)
|
| Rated impulse voltage (Uimp) |
Power circuit: 4 kV
|
| Output utilization category |
DC-1, DC-13 per IEC
|
| Input ON-state voltage (pin 4), nom |
10...26.4V DC @ 24V DC
|
| Input supply voltage |
Unswitched power A3/A2
|
| Type of inputs |
24V DC current sinking
|
| Concurrent explicit messages, max (CIP Class 3) |
Network connections: 6
|
| Input power terminals |
Power circuit: L1, L2, L3
|
| Motor power terminals |
Power circuit: T1, T2, T3
|
| Application |
Power circuit: three-phase
|
| Overload reset level |
Power circuit: 1...100% TCU
|
| DeviceLogix I/O response |
Input ratings: 2 ms @ 500 Hz
|
| Output load types |
Resistive or light inductive
|
| PE (earth ground) terminal |
Power circuit: 4 PE terminals
|
| Reset mode |
Power circuit: automatic/manual
|
| Input bounce filter (software configurable) |
OFF-ON or ON-OFF: 0.5 ms + 64 ms
|
| Class 1 connection API |
Network connections: 2...3200 ms
|
| Input connection type |
Single keyed M12, quick disconnect
|
| Output connection type |
Single keyed M12, quick disconnect
|
| Class 3 connection API |
Network connections: 100...10000 ms
|
| Security |
Web server: login and password configurable
|
| Power supply |
Control circuit (external source): NEC class 2
|
| Rated operating voltage, max |
Power circuit: 400Y/230...480Y/277 (-15%, +10%)
|
| Request packet interval (RPI) |
Network connections: 20 ms default (2 ms minimum)
|
| Rated operating voltage |
Control circuit (external source): 24V DC (+10%, -20%)
|
| Webpage features |
Web server: status, diagnostics and configuration tabs
|
| Output overcurrent protection |
1.5 A (the sum of all outputs cannot exceed this value)
|
|
Web server: support simple mail transfer protocol (SMTP)
|
|
| Output surge suppression |
Integrated diode to help protect against switching loads
|
| Overvoltage protection |
Control circuit (external source): reverse-polarity protected
|
| Sensor sourcing input current (pin 1), max |
50 mA per point (maximum 300 mA total for sourcing one device)
|
| Output current (each) |
Control circuit (external source): 500 mA @ switched power supply requirements
|
| Input current (each) |
Control circuit (external source): 50 mA @ unswitched power supply requirements
|
| Number of inputs (x 50 mA) |
Control circuit (external source): user defined @ switched and unswitched power supply requirements
|
| Number of outputs (x 500 mA) |
Control circuit (external source): user defined @ switched and unswitched power supply requirements
|
| I/O connections, max (CIP Class 1) |
Network connections: supports up to 2 class 1 CIP connections [exclusive owner (data) or listen-only]. One connection per PLC. Listen only connection requires a data connection to be established.
|
| Altitude |
2000 m
|
|---|---|
| Operating temperature |
-20 °C
|
| Storage and transportation temperature |
-25 °C
|
| Conducted emission |
EN 60947-4-1, Class A
|
| Humidity |
5...95% (noncondensing)
|
| Surge transient |
1 kV (12) L-L, 2 kV (2) L-N (earth)
|
| Radiated emissions |
EN 60947-4-1, Class A
|
| Radio frequency electromagnetic field |
EN 60947-4-1, 10V/m, 80 MHz...1 GHz, 10V/m, 1.4 GHz...2 GHz
|
| Degree of protection (NEMA) |
4
|
| Pollution degree |
3
|
| Radio frequency conducted disturbance immunity |
10V @ 150kHz...80 MHz
|
| Electrostatic discharge |
4 kV contact and 8 kV air
|
| Fast transient |
2 kV (power), 2 kV (PE), 1 kV (communications and control)
|
| 类型 | 资源 | 出版 |
|---|---|---|
| Selection Guide | 280-sg002_-en-p | 280-SG002 |
| Technical Data | 290-td001_-en-p | 290-TD001 |
| User Manual | 290d-um001_-en-p | 290D-UM001 |
| 常规 | Product Cutsheet | -- |
| 常规 | Wiring Diagrams | -- |
| 常规 | Specifications | -- |
| 常规 | Cicuit Protection Device And SCCR Tables | -- |
- CE
- China CCC
- Australian RCM
- UL Listed
- MOROCCO DOC
This product was certified with the above certifications as of 2025-10-26. Products sold before or after this date might carry different certifications. Please review the product label to check for the certifications your specific product carries.
技术规格
| Option 1 |
HOA Selector keypad
|
|---|
| Width |
260 mm
|
|---|---|
| Height |
217.83 mm
|
| Depth |
166.5 mm
|
| Number of poles |
Power circuit: 3
|
| Wire size |
Power terminal: (2) #18... AWG (0.8...5.2 mm²) per terminal
|
| Degree of protection (IP) |
IP66
|
|---|---|
| Shipping weight, approx |
4.6 kg
|
| Power rating |
Power terminal: 25A @ 600V AC
|
| Shock |
Opsal: 30 G, exceeds IEC 60947-1
|
| Gland plate options |
ArmorConnect power media connection (no cable)
|
| Wire strip length |
0.35 ±0.01 in (9 ±2 mm)
|
| Vibration |
Opsal: 2.5 G @ tested to MIL-STD-810G, exceeds IEC 60947-1
|
| Tightening torque |
Power terminal: 10.6 ±2 in-lb (1.2 ±0.2 Nm)
|
| Mechanical life operations |
Disconnect: 200000
|
| Disconnect lock out |
Maximum of 3/8 in (9.5 mm) diam lock shackle or hasp
|
| Contactor opening delay |
8 ms
|
| Contactor closing delay |
18 ms
|
| Wire type |
Multi-strand copper wire
|
| Disconnect LOTO locks |
Up to 2 locks or hasps are supported
|
| Contactor utilization category |
AC-1, AC-3, AC-4 per IEC (refer to life load curves)
|
| Baud rates |
500 kbps
|
|---|---|
| Communication |
DeviceNet
|
| Web server |
HTTP 1.1
|
| Input ON-state current (pin 4) |
2.6mA @ 24V DC
|
| DeviceNet input current surge |
500 mA @ peak inrush
|
| Operating dielectric withstand |
2000V AC per IEC
|
| DeviceNet input current |
50mA @ 24V DC
|
| Overvoltage category |
Power circuit: III
|
| Product type |
Full voltage starter
|
| Fuse rating |
CC, J, or T fuse (40 A, maximum)
|
| DeviceNet supply voltage rating |
Range 11...25V DC @ 24V DC nominal
|
| Insulation voltage (Ui) |
Output ratings: rated 2000V AC per IEC
|
| Rated operating current, max |
Power circuit: 0.24...3.5A @ 2Hp (1.5 kW)
|
| Rated input operation voltage |
24V DC
|
| Input OFF-state current |
<1.5 mA
|
| Input OFF-state voltage |
5V DC
|
| Distance, max |
500 m (1630 ft) @ 125 Kbps
|
| Operating frequency |
Power circuit: 50/60 Hz (±10%)
|
| User options 1 |
HAND-OFF-AUTO selector keypad
|
| Trip rating |
Power circuit: 120% of full load current (FLC) setting
|
| Application in industrial area permitted (SCPD list) |
Size per NFPA 70 (NEC) or NFPA 79 for group motor applications
|
| Short circuit coordination |
Type 1
|
| Overload type |
Power circuit: solid-state I²t
|
| Insulation voltage |
Rated 250V AC
|
| Dielectric withstand |
Power circuit: 2500V AC per IEC
|
| Concurrent TCP connections |
Network connections: maximum of 15 encapsulated messages over both TCP and UDP
|
| RMS symmetrical amperes |
10 kA @ 480Y/277 (short circuit current rating)
|
| Power |
Control circuit (external source): 6.6 W @ switched and unswitched power supply requirements
|
| Current, nom |
Control circuit (external source): 275 mA @ switched and unswitched power supply requirements
|
| Peak inrush |
Control circuit (external source): <5 A for 35 ms @ unswitched power supply requirements
|
| Voltage |
Control circuit (external source): 19.2...26.4V DC @ unswitched power supply requirements
|
| Trip class |
Power circuit: Class 10 (default), 15, 20 with thermal memory retention (see motor overload trip curves)
|
| Current, max |
Control circuit (external source): 450 mA @ unswitched power supply requirements
|
| Power, max |
Control circuit (external source): 6.6 W + (24V DC x user defined) @ switched and unswitched power supply requirements
|
| Supporting protocol for DeviceNet |
Yes
|
| Application in industrial area permitted |
Yes
|
| Mains frequency |
50/60 Hz
|
| Number of input devices, max |
6
|
| Output OFF-state leakage current, max |
1 µa
|
| Number of outputs, max |
6
|
| Number of configurable digital I/O |
6
|
| Input filtering |
100 µs
|
| OFF time, min |
200 ms
|
| Auto-baud rate identification |
Yes
|
| Group 2 - slave only device type |
Yes
|
| Polled I/O messaging |
Yes
|
| Change of state messaging |
Yes
|
| Cyclic messaging |
Yes
|
| Explicit messaging |
Yes
|
| Full parameter object support |
Yes
|
| Group 4 - off-line node recovery messaging |
Yes
|
| Configuring consistency value |
Yes
|
| Unconnected messaging manager (UCMN) |
Yes
|
| Output supply voltage (switched power) |
A1/A2
|
| Input per connection |
1/each
|
| Output per connection |
1/each
|
| Output blocking voltage, max |
35V DC
|
| Sensor input leakage current, max |
<2.5 mA
|
| Type of outputs |
DC sourcing
|
| Sensor input operating voltage |
19.2...26V DC
|
| Concurrent sessions |
Web server: 20
|
| Rated output operating voltage (Ue) |
19.2...26.4V DC
|
| Disconnect |
Motor disconnect
|
| Output operating current (Ie), nom |
500 mA per point
|
| Output thermal current (Ithe), max |
500 mA per point
|
| Connection type |
Quick disconnects
|
| Output state |
Normally open (NO)
|
| Rated impulse voltage (Uimp) |
Power circuit: 4 kV
|
| Output utilization category |
DC-1, DC-13 per IEC
|
| Input ON-state voltage (pin 4), nom |
10...26.4V DC @ 24V DC
|
| Input supply voltage |
Unswitched power A3/A2
|
| Type of inputs |
24V DC current sinking
|
| Concurrent explicit messages, max (CIP Class 3) |
Network connections: 6
|
| Input power terminals |
Power circuit: L1, L2, L3
|
| Motor power terminals |
Power circuit: T1, T2, T3
|
| Application |
Power circuit: three-phase
|
| Overload reset level |
Power circuit: 1...100% TCU
|
| DeviceLogix I/O response |
Input ratings: 2 ms @ 500 Hz
|
| Output load types |
Resistive or light inductive
|
| PE (earth ground) terminal |
Power circuit: 4 PE terminals
|
| Reset mode |
Power circuit: automatic/manual
|
| Input bounce filter (software configurable) |
OFF-ON or ON-OFF: 0.5 ms + 64 ms
|
| Class 1 connection API |
Network connections: 2...3200 ms
|
| Input connection type |
Single keyed M12, quick disconnect
|
| Output connection type |
Single keyed M12, quick disconnect
|
| Class 3 connection API |
Network connections: 100...10000 ms
|
| Security |
Web server: login and password configurable
|
| Power supply |
Control circuit (external source): NEC class 2
|
| Rated operating voltage, max |
Power circuit: 400Y/230...480Y/277 (-15%, +10%)
|
| Request packet interval (RPI) |
Network connections: 20 ms default (2 ms minimum)
|
| Rated operating voltage |
Control circuit (external source): 24V DC (+10%, -20%)
|
| Webpage features |
Web server: status, diagnostics and configuration tabs
|
| Output overcurrent protection |
1.5 A (the sum of all outputs cannot exceed this value)
|
|
Web server: support simple mail transfer protocol (SMTP)
|
|
| Output surge suppression |
Integrated diode to help protect against switching loads
|
| Overvoltage protection |
Control circuit (external source): reverse-polarity protected
|
| Sensor sourcing input current (pin 1), max |
50 mA per point (maximum 300 mA total for sourcing one device)
|
| Output current (each) |
Control circuit (external source): 500 mA @ switched power supply requirements
|
| Input current (each) |
Control circuit (external source): 50 mA @ unswitched power supply requirements
|
| Number of inputs (x 50 mA) |
Control circuit (external source): user defined @ switched and unswitched power supply requirements
|
| Number of outputs (x 500 mA) |
Control circuit (external source): user defined @ switched and unswitched power supply requirements
|
| I/O connections, max (CIP Class 1) |
Network connections: supports up to 2 class 1 CIP connections [exclusive owner (data) or listen-only]. One connection per PLC. Listen only connection requires a data connection to be established.
|
| Altitude |
2000 m
|
|---|---|
| Operating temperature |
-20 °C
|
| Storage and transportation temperature |
-25 °C
|
| Conducted emission |
EN 60947-4-1, Class A
|
| Humidity |
5...95% (noncondensing)
|
| Surge transient |
1 kV (12) L-L, 2 kV (2) L-N (earth)
|
| Radiated emissions |
EN 60947-4-1, Class A
|
| Radio frequency electromagnetic field |
EN 60947-4-1, 10V/m, 80 MHz...1 GHz, 10V/m, 1.4 GHz...2 GHz
|
| Degree of protection (NEMA) |
4
|
| Pollution degree |
3
|
| Radio frequency conducted disturbance immunity |
10V @ 150kHz...80 MHz
|
| Electrostatic discharge |
4 kV contact and 8 kV air
|
| Fast transient |
2 kV (power), 2 kV (PE), 1 kV (communications and control)
|
图纸
文档
|
280-sg002_-en-p
Selection Guide
280-SG002 |
|
290-td001_-en-p
Technical Data
290-TD001 |
|
290d-um001_-en-p
User Manual
290D-UM001 |
|
Product Cutsheet
常规
-- |
|
Wiring Diagrams
常规
-- |
|
Specifications
常规
-- |
|
Cicuit Protection Device And SCCR Tables
常规
-- |
| 类型 | 资源 | 出版 |
|---|---|---|
| Selection Guide | 280-sg002_-en-p | 280-SG002 |
| Technical Data | 290-td001_-en-p | 290-TD001 |
| User Manual | 290d-um001_-en-p | 290D-UM001 |
| 常规 | Product Cutsheet | -- |
| 常规 | Wiring Diagrams | -- |
| 常规 | Specifications | -- |
| 常规 | Cicuit Protection Device And SCCR Tables | -- |
认证
- CE
- China CCC
- Australian RCM
- UL Listed
- MOROCCO DOC
This product was certified with the above certifications as of 2025-10-26. Products sold before or after this date might carry different certifications. Please review the product label to check for the certifications your specific product carries.
配件
替代产品
技术说明
Loading
Copyright ©2026 Rockwell Automation, Inc.