Published Date: 8/14/2025
Last Updated: 8/14/2025
Revision Number: 1.0
CVSS Score: 9.0/10
The security of our products is important to us as your chosen industrial automation supplier. This anomaly was found internally during routine testing and is being reported based on our commitment to customer transparency and to improve their business or production environments.
AFFECTED PRODUCTS AND SOLUTION
Affected Product |
CVE |
Affected Software Versions |
Corrected in Software Version |
FactoryTalk Linx |
CVE-2025-7972 |
All prior to 6.50 |
6.50 and later |
VULNERABILITY DETAILS
Rockwell Automation used the latest version of the CVSS scoring system to assess the following vulnerabilities.
CVE-2025-7972 IMPACT
A security issue exists within the FactoryTalk Linx Network Browser. By modifying the process.env.NODE_ENV to ‘development’, the attacker can disable FTSP token validation. This bypass allows access to create, update, and delete FTLinx drivers.
CVSS 3.1 Base Score: 9.0
CVSS 3.1 Vector: CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:C/C:N/I:H/A:H
CVSS 4.0 Base Score: 8.4
CVSS 4.0 Vector: CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:N/VI:H/VA:H/SC:N/SI:H/SA:H
CWE: CWE-286: Incorrect User Management
Known Exploited Vulnerability (KEV) database: No
Mitigations and Workarounds
Users should update to the corrected version if possible. If users using the affected software are not able to upgrade the version, security best practices should be applied.
Glossary:
- FTSP: (FactoryTalk Services Platform) facilitates communication between FactoryTalk® components, enabling data exchange and interaction across computers in a FactoryTalk directory