Logix Controllers Vulnerable to Denial-of-Service Attack

Severity:
High
Advisory ID:
PN1609
发布日期:
December 06, 2022
上次更新时间:
October 16, 2024
Revision Number:
1.0
Known Exploited Vulnerability (KEV):
否
Corrected:
是
Workaround:
否
CVE IDs
CVE-2022-3752
下载
The following link(s) provide the security advisory in Vulnerability Exploitability Exchange format:
JSON
摘要
Logix Controllers Vulnerable to Denial-of-Service Attack

 

Revision History
Revision Number
1.0
Revision History
Version 1.0 – December 6, 2022

Executive Summary

Rockwell Automation discovered a vulnerability within our Logix Controllers.  This vulnerability may allow an unauthorized user to cause a denial of service on a targeted device.  Customers using affected versions of this firmware are encouraged to evaluate the following mitigations provided and apply them to their deployed products. Additional details relating to the discovered vulnerability, including affected products and recommended countermeasures, are provided in this security advisory.

Affected Products

  • CompactLogix 5380 controllers
  • Compact GuardLogix® 5380 controllers
  • CompactLogix 5480 controllers
  • ControlLogix 5580 controllers
  • GuardLogix 5580 controllers

Vulnerability Details

CVE-2022-3752 Rockwell Automation Logix Controllers are Vulnerable to a Denial-of-Service Attack
An unauthorized user could use a specially crafted sequence of Ethernet/IP messages, combined with heavy traffic loading  to cause a denial-of-service condition resulting in a major non-recoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online and continue normal operation.

CVSS v3.1 Base Score: 8.6/10[HIGH]
CVSS v3.1 Vector: AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H

Risk Mitigation & User Action

Customers using the products in scope are encouraged to evaluate the mitigations provided below and apply the appropriate mitigations to their deployed products.
Products Affected First Known Version Affected Corrected In
CompactLogix 5380 Compact GuardLogix 5380 ControlLogix 5580 GuardLogix 5580 This vulnerability is present in firmware version 31.011 and later This issue has been mitigated in the following firmware versions:
  • 32.016 and later for versions 32
  • 33.015 and later for versions 33
  • 34.011 and later
Customers should upgrade to a version listed above to mitigate this vulnerability
CompactLogix 5480 This vulnerability is present in firmware version 32.011 and later

General Security Guidelines

General security guidelines can be found in QA43240 - Recommended Security Guidelines Article in our Knowledgebase.

Requests for additional information can be sent to the PSIRT Inbox (PSIRT@rockwellautomation.com).

ADDITIONAL LINKS

  • PN1354 - Industrial Security Advisory Index
  • CVE-2022-3752 JSON

 

Rockwell Automation Home
Copyright ©2022 Rockwell Automation, Inc.
  1. Chevron LeftChevron Left Rockwell Automation 主页 Chevron RightChevron Right
  2. Chevron LeftChevron Left Trust Center Chevron RightChevron Right
  3. Chevron LeftChevron Left Industrial Security Adv Chevron RightChevron Right
  4. Chevron LeftChevron Left Industrial Security Advisory Detail Chevron RightChevron Right
请更新您的Cookies偏好以继续.
此功能需要Cookies来增强您的体验。请更新您的系统偏好以允许使用这些Cookies:
  • 社交媒体Cookies
  • 功能Cookies
  • 性能 Cookies
  • 市场营销Cookies
  • 所有Cookies
您可以随时更新您的系统偏好。如需了解更多信息,请参阅我们的 {0} 隐私政策
CloseClose