FactoryTalk Alarm and Events Server Vulnerable to Denial-Of-Service Attack

Severity:
High
Advisory ID:
PN1605
发布日期:
October 27, 2022
上次更新时间:
October 16, 2024
Revision Number:
1.0
Known Exploited Vulnerability (KEV):
否
Corrected:
否
Workaround:
是
CVE IDs
CVE-2022-38744
下载
The following link(s) provide the security advisory in Vulnerability Exploitability Exchange format:
JSON
摘要
FactoryTalk Alarm and Events Server Vulnerable to Denial-Of-Service Attack

 

Revision History
Revision History
Version 1.0 – October 27, 2022

Executive Summary

Rockwell Automation received a report from Kaspersky Labs regarding one vulnerability in FactoryTalk® Alarms and Events servers. If successfully exploited, these vulnerabilities may result in a denial-of-service condition causing the server to be unavailable.

Customers using affected versions of this software are encouraged to evaluate the following mitigations and apply them appropriately to their deployed products. Additional details relating to the discovered vulnerability, including affected products and recommended countermeasures, are provided.

Affected Products

FactoryTalk Alarms and Events server – All versions

Vulnerability Details

CVE-2022-38744 FactoryTalk Alarm and Events server vulnerable to denial-of-service attack
An unauthenticated attacker with network access to a victim's FactoryTalk service could open a connection, causing the service to fault and become unavailable. The affected port can be used as a server ping port and use messages structured with XML.

CVSS v3.1 Base Score: 7.5/10[MEDIUM]
CVSS v3.1 Vector: AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Risk Mitigation & User Action

Customers using the affected software are encouraged to set up the secondary mitigation as described below that addresses the associated risk. Customers are also directed towards general risk mitigation strategies provided in QA43240 - Recommended Security Guidelines from Rockwell Automation , in our Knowledgebase.
Vulnerability Suggested Actions
CVE-2022-38744 Customers should set up IPsec to mitigate this issue as detailed in QA46277 - Deploying FactoryTalk Software with IPsec

General Security Guidelines

General security guidelines can be found in QA43240 - Recommended Security Guidelines from Rockwell Automation .

Requests for additional information can be sent to the PSIRT Inbox (PSIRT@rockwellautomation.com).

Additional Links

  • PN1354 - Industrial Security Advisory Index
  • CVE-2022-38744 JSON

 

Rockwell Automation Home
Copyright ©2022 Rockwell Automation, Inc.
  1. Chevron LeftChevron Left Rockwell Automation 主页 Chevron RightChevron Right
  2. Chevron LeftChevron Left Trust Center Chevron RightChevron Right
  3. Chevron LeftChevron Left Industrial Security Adv Chevron RightChevron Right
  4. Chevron LeftChevron Left Industrial Security Advisory Detail Chevron RightChevron Right
请更新您的Cookies偏好以继续.
此功能需要Cookies来增强您的体验。请更新您的系统偏好以允许使用这些Cookies:
  • 社交媒体Cookies
  • 功能Cookies
  • 性能 Cookies
  • 市场营销Cookies
  • 所有Cookies
您可以随时更新您的系统偏好。如需了解更多信息,请参阅我们的 {0} 隐私政策
CloseClose