Consist Of | Screws |
---|---|
I/O Status Indication | None |
Number of analogue inputs | 4 |
---|---|
Resolution of the analogue inputs | 12 bit |
Input, current | True |
Input, voltage | True |
Input, resistor | False |
Input, resistance thermometer | False |
Input, thermocouple | False |
Input signal, configurable | False |
Output, current | False |
Output, voltage | False |
Output signal configurable | False |
Analogue inputs configurable | True |
Analogue outputs configurable | False |
Type of electric connection | Screw connection |
Data range | 0 to 65535 |
Channel to channel isolation | Non-isolation |
Update time | 180 ms per enabled channel |
Input group to bus isolation | No isolation |
Module error | Voltage: ±1.5% @ over full temperature range, -20...65°C (-4...149°F), Current: ±2.0% @ over full temperature range, -20...65°C (-4...149°F) |
Wire size | Solid: 0.14 mm2 AWG)...1.5 mm2 AWG) @ Rated @ 90 °C (194 °F) insulation maximum, Stranded: 0.14 mm2 AWG)...1.0 mm2 AWG) @ Rated @ 90 °C (194 °F) insulation maximum |
Suitable for safety functions | False |
SIL according to IEC 61508 | None |
Recommended maximum shielded cable length | 10 m |
Voltage ranges | 0 |
Current range | 0 mA |
Field input calibration | Not required |
Overall accuracy | Voltage terminal: ±1% full scale @ 25°C, Current terminal: ±1% full scale @ 25°C |
Surrounding air temperature, max | 65 °C |
---|---|
North American temperature code | T4 |
Power consumption | <60mA @ 3.3V |
Emissions | CISPR 11 (IEC 61000-6-4): Class A |
ESD immunity | IEC 61000-4-2: 6 kV contact discharges, 8 kV air discharges |
EFT/B immunity | IEC 61000-4-4: ±2kV @ 5kHz on shielded ports |
Relative humidity | IEC 60068-2-30 (Test Db, unpackaged dA heat), 5...95% noncondensing |
Conducted RF immunity | IEC 61000-4-6, 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz |
Surge transient immunity | IEC 61000-4-5: ±2 kV line-earth(CM) on shielded ports |
Operating temperature | -20...65 °C (-4...149 °F): IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, operating dry heat), IEC 60068-2-14 (Test Nb, operating thermal shock) |
Radiated RF immunity | IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10V/m with 200 Hz 50% pulse 100% AM @ 900 MHz, 10V/m with 200 Hz 50% pulse 100% AM @ 1890 MHz, 10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz, |
Operating altitude | 2000 m |
Nonoperating temperature | -40...85 °C (-40...185 °F), IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) |
Non-linearity | ±0.1% @ in % full scale |
---|
Repeatability | ±0.1% |
---|
Vibration | IEC 60068-2-6 (Test Fc, operating), 2 G @ 10...500 Hz |
---|---|
Shock | IEC 60068-2-27 (Test Ea, unpackaged shock): DIN rail mount: 25 g, nonoperating, Panel Mount: 35 g nonoperating |
Mounting torque | 0.2 nm |
Terminal screw torque | 0.22...0.25 Nm (1.95...2.21 in-lb) (using a 2.5 mm (0.10 in.) flat-blade screwdriver) |
Input impedance | >100 kΩ for voltage mode, 250 Ω for current mode |
---|
Explosion safety category for gas | None |
---|---|
Explosion safety category for dust | None |
图纸 | |
---|---|
3D STP (STEP) Model | Download (ZIP) |
Product Drawing | Drawing (DXF) |
图纸 |
---|
3D STP (STEP) Model Download (ZIP) |
Product Drawing Drawing (DXF) |
登录您的罗克韦尔自动化帐户以查看和下载技术图纸.
登录
类型 | 资源 | 出版 |
---|---|---|
General | Product Cutsheet | -- |
General | Wiring Diagram | -- |
General | Installation Guide | -- |
General | Brochure | -- |
User Manual | 2080-um004_-en-e | 2080-UM004 |
User Manual | Micro800 Plug-in Modules User Manual | 2080-UM002 |
- Korean Register of Shippin
- Bureau Veritas
This product was certified with the above certifications as of 2025-09-09. Products sold before or after this date might carry different certifications. Please review the product label to check for the certifications your specific product carries.
技术规格
Consist Of | Screws |
---|---|
I/O Status Indication | None |
Number of analogue inputs | 4 |
---|---|
Resolution of the analogue inputs | 12 bit |
Input, current | True |
Input, voltage | True |
Input, resistor | False |
Input, resistance thermometer | False |
Input, thermocouple | False |
Input signal, configurable | False |
Output, current | False |
Output, voltage | False |
Output signal configurable | False |
Analogue inputs configurable | True |
Analogue outputs configurable | False |
Type of electric connection | Screw connection |
Data range | 0 to 65535 |
Channel to channel isolation | Non-isolation |
Update time | 180 ms per enabled channel |
Input group to bus isolation | No isolation |
Module error | Voltage: ±1.5% @ over full temperature range, -20...65°C (-4...149°F), Current: ±2.0% @ over full temperature range, -20...65°C (-4...149°F) |
Wire size | Solid: 0.14 mm2 AWG)...1.5 mm2 AWG) @ Rated @ 90 °C (194 °F) insulation maximum, Stranded: 0.14 mm2 AWG)...1.0 mm2 AWG) @ Rated @ 90 °C (194 °F) insulation maximum |
Suitable for safety functions | False |
SIL according to IEC 61508 | None |
Recommended maximum shielded cable length | 10 m |
Voltage ranges | 0 |
Current range | 0 mA |
Field input calibration | Not required |
Overall accuracy | Voltage terminal: ±1% full scale @ 25°C, Current terminal: ±1% full scale @ 25°C |
Surrounding air temperature, max | 65 °C |
---|---|
North American temperature code | T4 |
Power consumption | <60mA @ 3.3V |
Emissions | CISPR 11 (IEC 61000-6-4): Class A |
ESD immunity | IEC 61000-4-2: 6 kV contact discharges, 8 kV air discharges |
EFT/B immunity | IEC 61000-4-4: ±2kV @ 5kHz on shielded ports |
Relative humidity | IEC 60068-2-30 (Test Db, unpackaged dA heat), 5...95% noncondensing |
Conducted RF immunity | IEC 61000-4-6, 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz |
Surge transient immunity | IEC 61000-4-5: ±2 kV line-earth(CM) on shielded ports |
Operating temperature | -20...65 °C (-4...149 °F): IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, operating dry heat), IEC 60068-2-14 (Test Nb, operating thermal shock) |
Radiated RF immunity | IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10V/m with 200 Hz 50% pulse 100% AM @ 900 MHz, 10V/m with 200 Hz 50% pulse 100% AM @ 1890 MHz, 10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz, |
Operating altitude | 2000 m |
Nonoperating temperature | -40...85 °C (-40...185 °F), IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) |
Non-linearity | ±0.1% @ in % full scale |
---|
Repeatability | ±0.1% |
---|
Vibration | IEC 60068-2-6 (Test Fc, operating), 2 G @ 10...500 Hz |
---|---|
Shock | IEC 60068-2-27 (Test Ea, unpackaged shock): DIN rail mount: 25 g, nonoperating, Panel Mount: 35 g nonoperating |
Mounting torque | 0.2 nm |
Terminal screw torque | 0.22...0.25 Nm (1.95...2.21 in-lb) (using a 2.5 mm (0.10 in.) flat-blade screwdriver) |
Input impedance | >100 kΩ for voltage mode, 250 Ω for current mode |
---|
Explosion safety category for gas | None |
---|---|
Explosion safety category for dust | None |
图纸
图纸 | |
---|---|
3D STP (STEP) Model | Download (ZIP) |
Product Drawing | Drawing (DXF) |
图纸 |
---|
3D STP (STEP) Model Download (ZIP) |
Product Drawing Drawing (DXF) |
登录您的罗克韦尔自动化帐户以查看和下载技术图纸.
登录
文档
Product Cutsheet
General
-- |
Wiring Diagram
General
-- |
Installation Guide
General
-- |
Brochure
General
-- |
2080-um004_-en-e
User Manual
2080-UM004 |
Micro800 Plug-in Modules User Manual
User Manual
2080-UM002 |
类型 | 资源 | 出版 |
---|---|---|
General | Product Cutsheet | -- |
General | Wiring Diagram | -- |
General | Installation Guide | -- |
General | Brochure | -- |
User Manual | 2080-um004_-en-e | 2080-UM004 |
User Manual | Micro800 Plug-in Modules User Manual | 2080-UM002 |
认证
- Korean Register of Shippin
- Bureau Veritas
This product was certified with the above certifications as of 2025-09-09. Products sold before or after this date might carry different certifications. Please review the product label to check for the certifications your specific product carries.
技术说明
Loading