1783-BMS06SA
Stratix 5700 6 Port Managed Switch
Rockwell Automation announces that as of September 01, 2024, the Stratix 5700 6 Port Managed Switch will be discontinued and no longer available for sale. Customers are encouraged to remove references to the affected product(s)
停产日期:
September 01, 2024
替代类别:
Engineering Replacement
替代产品:
1783-CMS6P
[https://www.rockwellautomation.com.cn/products/details.1783-CMS6P.html]
Product at a glance
Rockwell Automation announces that as of September 01, 2024, the Stratix 5700 6 Port Managed Switch will be discontinued and no longer available for sale. Customers are encouraged to remove references to the affected product(s)
停产日期:
September 01, 2024
替代类别:
Engineering Replacement
替代产品:
1783-CMS6P
[https://www.rockwellautomation.com.cn/products/details.1783-CMS6P.html]
Product at a glance
| Port |
6
|
|---|
| Width |
7.48 cm
|
|---|---|
| Height |
12.95 cm
|
| Depth |
11.67 cm
|
| Approximate weight |
1.11 kg
|
| Screw torque, ground terminal, maximum |
0.96 nm
|
| Screw torque, power and alarm terminals |
0.23 nm
|
| Number of ports 10/100 Mbps RJ45 |
4
|
|---|---|
| Layer 2 |
No
|
| Layer 3 |
No
|
| Manageable |
Yes
|
| Power consumption, maximum |
15 W
|
| Power dissipation |
15 W
|
| Firmware type |
Full
|
| Isolation voltage (continuous), basic insulation type, DC power ports to ground, DC power ports to ethernet ports, and DC power ports to alarm ports |
50 V
|
| Number of ports 10/100 Mbps SFP |
2
|
| Power consumption at 24V DC, 40 ˚C |
9.5 W
|
| Total number of ports |
6
|
| Wire size, alarm connection, solid or stranded, UL/CSA-rated style 1007 or 1569 twisted-pair copper appliance wiring material (AWM) wire |
0.5 mm²
|
| Wire size, DC power connection, solid or stranded copper wire rated at 75 °C or greater |
0.5 mm²
|
| Wire size, ethernet connection |
RJ45 connector according to IEC 60603-7, 2 or 4-pair category 5e minimum cable according to TIA 568-B.1 or category 5 cable according to ISO/IEC 24702
|
| Mounting method |
DIN rail (top hat rail)
|
| Ethernet |
Yes
|
| Protection type |
Alarm not rated
|
| Alarm relay at 30V DC |
1 A
|
| Alarm relay at 48V DC |
0.5 A
|
| Maximum insulation, DC power connection |
1.2 mm
|
| Power input at 12 - 48V DC, class 2/SELV |
0.5 A
|
| Wire size, ground connection, stranded copper wire, minimum |
4 mm²
|
| Wire strip length, alarm connection |
6.3±0.5
|
| Wire strip length, DC power connection |
6.3±0.5
|
| Wiring category on console and alarm ports |
3
|
| Wiring category on DC power ports |
2
|
| Wiring category on Ethernet ports |
2
|
| Degree of protection (IP) |
IP30
|
|---|---|
| Housing base material |
Open-style
|
| Nominal position |
T4
|
| Temperature, surrounding air, maximum |
60 °C
|
| EFT/B immunity for IEC 61000-4-4 at 100 kHz on DC power ports |
±2
|
| EFT/B immunity for IEC 61000-4-4 at 100 kHz on Ethernet ports |
±1
|
| EFT/B immunity for IEC 61000-4-4 at 5 kHz on alarm ports |
±2
|
| EFT/B immunity for IEC 61000-4-4 at 5 kHz on Ethernet ports |
±2
|
| Emissions, CISPR11 (IEC 61000-6-4) |
Class A
|
| ESD immunity, IEC 61000-4-2, air discharges |
15 kV
|
| ESD immunity, IEC 61000-4-2, contact discharges |
8 kV
|
| Radiated RF immunity, IEC 61000-4-3 with 1 kHz sine-wave 80% AM from 1000 - 2700 MHz |
10 kg/km
|
| Radiated RF immunity, IEC 61000-4-3 with 200 Hz 50% pulse 100% AM at 900 MHz |
20 kg/km
|
| Shock, non-operating, IEC 60068-2-27 (test Ea, unpackaged shock) |
55 g
|
| Shock, operating, IEC 60068-2-27 (test Ea, unpackaged shock) |
30 g
|
| Surge transient immunity, IEC 61000-4-5, line-earth (CM) on Ethernet ports |
±2
|
| Temperature, operating, IEC 60068-2-1 (test Ad, operating, cold) |
-40 °C
|
| Temperature, operating, IEC 60068-2-14 (test Nb, operating, thermal shock) |
-40 °C
|
| Temperature, operating, IEC 60068-2-2 (test Bd, operating, dry heat) |
-40 °C
|
| Selectable start times |
T4
|
| Conducted RF immunity, IEC 61000-4-6 with 1 kHz sine-wave 80% AM from 150 kHz - 80 MHz (rms) |
10 V
|
| Damped oscillatory wave immunity, IEC 61000-4-18, line-earth (CM) on power ports |
±2.5
|
| Damped oscillatory wave immunity, IEC 61000-4-18, line-line (DM) on power ports |
±1
|
| EFT/B immunity for IEC 61000-4-4 at 100 kHz on alarm ports |
±1
|
| EFT/B immunity for IEC 61000-4-4 at 2.5 kHz on alarm ports |
±4
|
| EFT/B immunity for IEC 61000-4-4 at 2.5 kHz on Ethernet ports |
±4
|
| EFT/B immunity for IEC 61000-4-4 at 5 kHz on DC power ports |
±4
|
| Radiated RF immunity, IEC 61000-4-3 with 1 kHz sine-wave 80% AM from 80 - 1000 MHz |
20 kg/km
|
| Relative humidity, IEC 60068-2-30 (test Db, unpackaged damp heat), non-condensing |
5 %
|
| Surge transient immunity, IEC 61000-4-5, line-earth (CM) on DC power ports |
±2
|
| Surge transient immunity, IEC 61000-4-5, line-line (DM) on DC power ports |
±1
|
| Temperature, non-operating, IEC 60068-2-1 (test Ab, unpackaged non-operating cold) |
-40 °C
|
| Temperature, non-operating, IEC 60068-2-14 (test Na, unpackaged non-operating thermal shock) |
-40 °C
|
| Temperature, non-operating, IEC 60068-2-2 (test Bb, unpackaged non-operating dry heat) |
-40 °C
|
| Vibration, IEC 60068-2-6 (test Fc, operating) at 10 - 500 Hz |
2 g
|
| Voltage variation IEC 61000-4-29, interruption on DC power ports |
10 ms
|
| 类型 | 资源 | 出版 |
|---|---|---|
| Application Techniques | APPLICATION_TECHNIQUES_enet-at007_-en-p | ENET-AT007 |
| Application Techniques | APPLICATION_TECHNIQUES_enet-at006_-en-p | ENET-AT006 |
| Installation Instructions | 1783-in016_-en-p | 1783-IN016 |
| Reference Manual | REFERENCE_MANUAL_enet-rm002_-en-p | ENET-RM002 |
| Technical Data | 1783-td002_-en-p | 1783-TD002 |
| User Manual | 1783-um004_-en-p | 1783-UM004 |
| User Manual | USER_MANUAL_1783-um007_-en-p | 1783-UM007 |
| 个人资料 | PROFILE_migrat-pp043_-en-p | MIGRAT-PP043 |
- China CCC
- UKCA DOC
- MOROCCO DOC
- UK EX CERTIFICATE
This product was certified with the above certifications as of 2025-11-20. Products sold before or after this date might carry different certifications. Please review the product label to check for the certifications your specific product carries.
技术规格
| Port |
6
|
|---|
| Width |
7.48 cm
|
|---|---|
| Height |
12.95 cm
|
| Depth |
11.67 cm
|
| Approximate weight |
1.11 kg
|
| Screw torque, ground terminal, maximum |
0.96 nm
|
| Screw torque, power and alarm terminals |
0.23 nm
|
| Number of ports 10/100 Mbps RJ45 |
4
|
|---|---|
| Layer 2 |
No
|
| Layer 3 |
No
|
| Manageable |
Yes
|
| Power consumption, maximum |
15 W
|
| Power dissipation |
15 W
|
| Firmware type |
Full
|
| Isolation voltage (continuous), basic insulation type, DC power ports to ground, DC power ports to ethernet ports, and DC power ports to alarm ports |
50 V
|
| Number of ports 10/100 Mbps SFP |
2
|
| Power consumption at 24V DC, 40 ˚C |
9.5 W
|
| Total number of ports |
6
|
| Wire size, alarm connection, solid or stranded, UL/CSA-rated style 1007 or 1569 twisted-pair copper appliance wiring material (AWM) wire |
0.5 mm²
|
| Wire size, DC power connection, solid or stranded copper wire rated at 75 °C or greater |
0.5 mm²
|
| Wire size, ethernet connection |
RJ45 connector according to IEC 60603-7, 2 or 4-pair category 5e minimum cable according to TIA 568-B.1 or category 5 cable according to ISO/IEC 24702
|
| Mounting method |
DIN rail (top hat rail)
|
| Ethernet |
Yes
|
| Protection type |
Alarm not rated
|
| Alarm relay at 30V DC |
1 A
|
| Alarm relay at 48V DC |
0.5 A
|
| Maximum insulation, DC power connection |
1.2 mm
|
| Power input at 12 - 48V DC, class 2/SELV |
0.5 A
|
| Wire size, ground connection, stranded copper wire, minimum |
4 mm²
|
| Wire strip length, alarm connection |
6.3±0.5
|
| Wire strip length, DC power connection |
6.3±0.5
|
| Wiring category on console and alarm ports |
3
|
| Wiring category on DC power ports |
2
|
| Wiring category on Ethernet ports |
2
|
| Degree of protection (IP) |
IP30
|
|---|---|
| Housing base material |
Open-style
|
| Nominal position |
T4
|
| Temperature, surrounding air, maximum |
60 °C
|
| EFT/B immunity for IEC 61000-4-4 at 100 kHz on DC power ports |
±2
|
| EFT/B immunity for IEC 61000-4-4 at 100 kHz on Ethernet ports |
±1
|
| EFT/B immunity for IEC 61000-4-4 at 5 kHz on alarm ports |
±2
|
| EFT/B immunity for IEC 61000-4-4 at 5 kHz on Ethernet ports |
±2
|
| Emissions, CISPR11 (IEC 61000-6-4) |
Class A
|
| ESD immunity, IEC 61000-4-2, air discharges |
15 kV
|
| ESD immunity, IEC 61000-4-2, contact discharges |
8 kV
|
| Radiated RF immunity, IEC 61000-4-3 with 1 kHz sine-wave 80% AM from 1000 - 2700 MHz |
10 kg/km
|
| Radiated RF immunity, IEC 61000-4-3 with 200 Hz 50% pulse 100% AM at 900 MHz |
20 kg/km
|
| Shock, non-operating, IEC 60068-2-27 (test Ea, unpackaged shock) |
55 g
|
| Shock, operating, IEC 60068-2-27 (test Ea, unpackaged shock) |
30 g
|
| Surge transient immunity, IEC 61000-4-5, line-earth (CM) on Ethernet ports |
±2
|
| Temperature, operating, IEC 60068-2-1 (test Ad, operating, cold) |
-40 °C
|
| Temperature, operating, IEC 60068-2-14 (test Nb, operating, thermal shock) |
-40 °C
|
| Temperature, operating, IEC 60068-2-2 (test Bd, operating, dry heat) |
-40 °C
|
| Selectable start times |
T4
|
| Conducted RF immunity, IEC 61000-4-6 with 1 kHz sine-wave 80% AM from 150 kHz - 80 MHz (rms) |
10 V
|
| Damped oscillatory wave immunity, IEC 61000-4-18, line-earth (CM) on power ports |
±2.5
|
| Damped oscillatory wave immunity, IEC 61000-4-18, line-line (DM) on power ports |
±1
|
| EFT/B immunity for IEC 61000-4-4 at 100 kHz on alarm ports |
±1
|
| EFT/B immunity for IEC 61000-4-4 at 2.5 kHz on alarm ports |
±4
|
| EFT/B immunity for IEC 61000-4-4 at 2.5 kHz on Ethernet ports |
±4
|
| EFT/B immunity for IEC 61000-4-4 at 5 kHz on DC power ports |
±4
|
| Radiated RF immunity, IEC 61000-4-3 with 1 kHz sine-wave 80% AM from 80 - 1000 MHz |
20 kg/km
|
| Relative humidity, IEC 60068-2-30 (test Db, unpackaged damp heat), non-condensing |
5 %
|
| Surge transient immunity, IEC 61000-4-5, line-earth (CM) on DC power ports |
±2
|
| Surge transient immunity, IEC 61000-4-5, line-line (DM) on DC power ports |
±1
|
| Temperature, non-operating, IEC 60068-2-1 (test Ab, unpackaged non-operating cold) |
-40 °C
|
| Temperature, non-operating, IEC 60068-2-14 (test Na, unpackaged non-operating thermal shock) |
-40 °C
|
| Temperature, non-operating, IEC 60068-2-2 (test Bb, unpackaged non-operating dry heat) |
-40 °C
|
| Vibration, IEC 60068-2-6 (test Fc, operating) at 10 - 500 Hz |
2 g
|
| Voltage variation IEC 61000-4-29, interruption on DC power ports |
10 ms
|
文档
|
APPLICATION_TECHNIQUES_enet-at007_-en-p
Application Techniques
ENET-AT007 |
|
APPLICATION_TECHNIQUES_enet-at006_-en-p
Application Techniques
ENET-AT006 |
|
1783-in016_-en-p
Installation Instructions
1783-IN016 |
|
REFERENCE_MANUAL_enet-rm002_-en-p
Reference Manual
ENET-RM002 |
|
1783-td002_-en-p
Technical Data
1783-TD002 |
|
1783-um004_-en-p
User Manual
1783-UM004 |
|
USER_MANUAL_1783-um007_-en-p
User Manual
1783-UM007 |
|
PROFILE_migrat-pp043_-en-p
个人资料
MIGRAT-PP043 |
| 类型 | 资源 | 出版 |
|---|---|---|
| Application Techniques | APPLICATION_TECHNIQUES_enet-at007_-en-p | ENET-AT007 |
| Application Techniques | APPLICATION_TECHNIQUES_enet-at006_-en-p | ENET-AT006 |
| Installation Instructions | 1783-in016_-en-p | 1783-IN016 |
| Reference Manual | REFERENCE_MANUAL_enet-rm002_-en-p | ENET-RM002 |
| Technical Data | 1783-td002_-en-p | 1783-TD002 |
| User Manual | 1783-um004_-en-p | 1783-UM004 |
| User Manual | USER_MANUAL_1783-um007_-en-p | 1783-UM007 |
| 个人资料 | PROFILE_migrat-pp043_-en-p | MIGRAT-PP043 |
认证
- China CCC
- UKCA DOC
- MOROCCO DOC
- UK EX CERTIFICATE
This product was certified with the above certifications as of 2025-11-20. Products sold before or after this date might carry different certifications. Please review the product label to check for the certifications your specific product carries.
替代产品
技术说明
Loading